24/7 electrical, heating, and cooling help across North Jersey

Call 973.809.2339

Load bank testing · Emergency and standby generators

Generator load bank testing in Essex County, New Jersey

MDL Electric Cooling & Heating does generator load bank testing for buildings in Essex, Morris and Union counties, New Jersey. That means nursing homes, medical buildings, apartment buildings, schools, offices, data rooms and municipal buildings. The test puts a measured load on the generator and records how it holds up.

A blue portable load bank on a concrete pad, with cables on black, red, blue and green connectors plugged into its Phase A, B, C and ground inputs

Why buildings book this test

A load bank test proves the generator can carry real load before an outage asks it to.

What MDL does. MDL does generator load bank testing for commercial standby and emergency generators. It also installs and services commercial standby generators. MDL confirms the scope after checking the generator's nameplate, its test records and where a load bank can connect.

Who books it. Nursing homes and assisted living. Outpatient and medical buildings. Apartment buildings with elevators and fire pumps on emergency power. Schools, offices, data and telecom rooms, and municipal buildings across Essex, Morris and Union counties (towns).

Why the building's own load often falls short. A diesel emergency generator must reach 30 percent of its standby nameplate kW on its monthly runs. A set sized for its largest motor or for future growth may never see that load on an ordinary day. The fix the standard allows is a supplemental load bank (the testing calendar).

Start here. MDL works from 4 Harrison Avenue in West Orange. Call 973.809.2339 or use the request form. A new system is on the commercial generator installation page. Repairs and routine service are on generator repair and maintenance.

The nameplateStandby kW, kVA, voltage and phase, from the generator's data plate.
The monthly logsThe kW reached on recent monthly runs, which shows whether the 30 percent rule is being met.
The hour meterThe current reading, and the testing hours registered with NJDEP if the engine has a general permit.
The connection pointA load bank breaker, docking station or connection box, if the building has one.

The testing calendar

Monthly, yearly and every 36 months: the loads and times the standards set.

NFPA 110 is the standard for emergency and standby power systems. Each row names the edition its numbers come from. The building's code official, insurer or accreditor decides which edition applies to a given building.

Scroll sideways to see the whole table.

Generator test schedule by edition.
TestLoad and timeApplies toSource
Monthly exercise, dieselAt least 30 minutes at 30 percent or more of the standby nameplate kW, or at the manufacturer's minimum exhaust gas temperature. Warm-up and cool-down do not count.Diesel emergency generatorsNFPA 110 (2010) 8.4.2
Monthly exercise, gas or propaneThe available load for 30 minutes, or until water temperature and oil pressure stabilizeSpark-ignited generatorsNFPA 110 (2010) 8.4.2
Annual supplemental load test50 percent of nameplate kW for 30 continuous minutes, then 75 percent for 1 continuous hour: 1.5 continuous hours in allDiesel sets whose monthly runs fall short of the 30 percent ruleNFPA 110 (2019) 8.4.2.3
36-month testContinuous for the system's assigned class, up to 4 hours; diesel at 30 percent or more of standby nameplate kWLevel 1 systems, where a failure could cost lives or cause serious injuryNFPA 110 (2010) 8.4.9
Combined testThe first 3 hours at the 36-month minimum, the last hour at 75 percent or moreThe 36-month and annual tests run as oneNFPA 110 (2010) 8.4.9
Health care interval12 generator tests a year, 20 to 40 days apartHealth care facilities under NFPA 99NFPA 99 (2012) 6.4.4.1.1.4(A)
New Jersey annual testAt least once a year, to the manufacturer's specifications, under anticipated load; transfer in 10 seconds or lessRequired emergency generatorsIFC 1203.4.2.1 as added by N.J.A.C. 5:70-3.2

Table sources, read November 16, 2026: Minnesota Department of Health (citing NFPA 110, 2010, and NFPA 99, 2012; revised June 2024), the Generac white paper (quoting NFPA 110, 2019, 8.4.2.3) and N.J.A.C. 5:70-3.2.

  • A 100 kW standby set, worked through. Monthly runs need at least 30 kW. An annual supplemental test holds 50 kW for 30 minutes, then 75 kW for an hour. These are our arithmetic on the NFPA percentages above.
  • Use the standby rating. NFPA's annex warns that a 100 kW standby set is often rated 80 kW for prime power. Thirty percent of the wrong figure is 24 kW, not 30 kW, so keep a permanent record of the rating.NFPA 110 first draft report
  • A load bank is allowed. NFPA 110 permits a supplemental load bank to meet or exceed the 30 percent monthly requirement.NFPA 110 first draft report
  • Why sets fall short. Minnesota's health department notes the gap appears when a large generator serves a small load, sized for its largest motor or for future expansion.Minnesota Department of Health
  • How the monthly test starts. It begins by simulating a power outage at the transfer switch test function or by opening a normal breaker.Minnesota Department of Health

Wet stacking

A diesel that only idles through its tests collects unburned fuel in the exhaust.

NFPA's annex to the monthly test rule names the problem. "Light loading creates a condition termed wet stacking, indicating the presence of unburned fuel or carbon, or both, in the exhaust system" (NFPA 110, annex A.8.4.2). The 30 percent monthly loading exists to reduce it.

  • The visible sign. NFPA says wet stacking is readily indicated by continuous black smoke while the engine runs.NFPA 110 annex
  • What heavy deposits do. They can restrict exhaust flow and raise back pressure. That can reduce output or even shut the engine down. They can also foul emission controls and, in some conditions, present a fire hazard.Avtron Power Solutions
  • Why a load test helps. Generac's white paper says the full-load operation of a load bank test burns off excess soot and moisture. It recommends diesel systems be load tested with a portable load bank for at least two hours a year.Generac white paper
  • Gas engines too. The same paper says natural gas generators also need load bank tests, to burn deposits out once the engine reaches operating temperature.Generac white paper
  • Smoke is also an air permit question. NJDEP's general permit for diesel emergency generators bars smoke darker than number 1 on the Ringelmann chart, or over 20 percent opacity, for more than 10 consecutive seconds.NJDEP GP-005A, item 3

Nursing homes and medical buildings

Health care adds a federal rule, an accreditor's checklist and a tighter monthly interval.

A nursing home or medical building answers to more than NFPA 110. These are the testing lines its surveyors read.

A U.S. Army Corps of Engineers team member in a hard hat looks at the meters and selector switches on a temporary generator's open control panel
Photo: a U.S. Army Corps of Engineers team member checks a temporary generator's meters during the Hurricane Ike power mission in Texas, 2008, which kept facilities such as hospitals running (U.S. Army Corps of Engineers, public domain), maker name blurred. Shown for illustration, not an MDL job.
  • CMS, for nursing homes. A long-term care facility must implement the generator inspection, testing and maintenance requirements of NFPA 99, NFPA 110 and the Life Safety Code.42 CFR 483.73(e)(2)
  • Monthly, under load. The Joint Commission's EC.02.05.07 EP 5 calls for each emergency generator to be tested monthly for 30 continuous minutes under load, plus cool-down.Joint Commission document list
  • The 30 percent fork. EP 6 asks for a diesel monthly load of at least 30 percent of nameplate, or the manufacturer's exhaust temperature. Otherwise, a test every 12 months at 50 percent for 30 minutes, then 75 percent for 60 minutes.Joint Commission document list
  • Every 36 months. EP 9 and EP 10 call for a four-hour generator load test at least once every 36 months, at 30 percent of nameplate or more.Joint Commission document list
  • Twelve a year. NFPA 99 asks health care facilities to test generator sets 12 times a year, 20 to 40 days apart.Minnesota Department of Health

New Jersey's rules for test runs

The state fire code, the electrical subcode and NJDEP's air permits each touch a test day.

Read November 16, 2026 from N.J.A.C. 5:70 (the Uniform Fire Code, Legal Information Institute copy), N.J.A.C. 5:23-3.16 (NJ Department of Community Affairs, published through August 17, 2026), the Construction Code Communicator and NJDEP's general permits. Your fire official, construction office and NJDEP decide edge cases.

Scroll sideways to see the whole table.

New Jersey generator test rules by section.
TopicWhat the rule saysSection
Which fire codeNew Jersey adopts the 2018 International Fire Code as its State Fire Prevention Code, with state changes.5:70-3.1(a)
Annual generator testRequired emergency generators are tested at least annually, to the manufacturer's specifications, under anticipated load conditions.IFC 1203.4.2.1, added by 5:70-3.2
Transition testOnce a year, a test confirms the transfer from normal to emergency power takes 10 seconds or less.IFC 1203.4.2.1 item 1
Fuel on siteAn engine-driven emergency generator keeps fuel for at least 2 hours of full-demand operation.IFC 1203.4.2.1 item 2
Which electrical codeThe National Electrical Code 2023, with Tentative Interim Amendments 70-23-1 through 70-23-13, is the state electrical subcode.5:23-3.16(a)1
Witnessed test at completionFor emergency and legally required standby systems, the local enforcing agency conducts or witnesses the test of the complete system. Article 702 has no similar requirement.NEC 700.3(A), 701.3(A), per DCA
Test hoursTesting and maintenance hours are capped at the hours registered, never more than 100 a year per generator, on a non-resettable hour meter.GP-005A and GP-005B
Test logEach test run records the reason, the date with start-up and shutdown times, the total time from the hour meter and the operator's name. Records are kept at least five years.GP-005A
Air quality daysNo routine testing when NJDEP forecasts air quality anywhere in New Jersey as unhealthy for sensitive groups or worse. Check after 4:00 p.m. the day before.GP-005A item 10; NJDEP forecast page
Real emergenciesAn emergency generator can run whenever it is needed for a true emergency, whatever the air quality.NJDEP forecast page

Table sources: N.J.A.C. 5:70-3.1 and 5:70-3.2; N.J.A.C. 5:23-3.16; the Construction Code Communicator, Spring 2021; NJDEP GP-005A, GP-005B and the air quality forecast page.

GP-005A covers emergency generators burning diesel, No. 2 fuel oil or kerosene. GP-005B covers natural gas or propane. A load bank run is a testing run, so it counts toward the registered hours and goes in the log.

On the test day

How a load bank test runs, from the first record check to the transfer test.

The order below follows EC&M's procedure for a portable load bank and Generac's white paper. MDL confirms the steps for each building after checking its generator and switchgear.

01

Records first

The standby kW rating, recent monthly logs, the hour meter and the NJDEP registered hours.

02

The forecast

NJDEP's air quality forecast, checked after 4:00 p.m. the day before.

03

The connection

A dedicated breaker, bus or connection box, with building loads left connected.

04

Warm-up

The generator runs until its water temperature stabilizes.

05

Step loading

Load is added in increments up to the target, never all at once.

06

Readings

Volts and amps per phase, frequency, kW, oil pressure and temperatures at each step.

07

Unload and cool

Load bank load comes off first, transfer switches go back to normal, and the engine cools down.

08

Transfer test

Generac recommends a transfer test after the load bank test, to prove the whole system.

  • Never unplug the output cables mid-test. If normal power failed, there would be no way to reconnect them within the 10 seconds life safety loads require.EC&M, Dan Chisholm Sr.
  • Test load gives way to real load. NFPA 110 requires equivalent test loads to be replaced automatically with the emergency loads if the primary source fails.EC&M, quoting NFPA 110 8.4.2.2
  • Where it connects. EC&M names a dedicated bus downstream of an overcurrent device in a switchboard, or a bus in an outdoor NEMA 3R connection box.EC&M
  • A docking station can do double duty. NEC 700.3(F) permits the permanent switching means for a temporary generator to be used to connect a load bank. Its connection point is marked with phase rotation and bonding, and interlocked.NEC 700.3(F), as quoted by Trystar
A gray disconnect switch with a red handle and a round plug-in connector mounted on a building's siding, above a small shingled enclosure
Photo: outdoor electrical fixtures that control a backup power generator at a national wildlife refuge building, 2014 (U.S. Fish and Wildlife Service, public domain), maker label blurred. Shown for illustration, not an MDL job.

Resistive or reactive

A resistive bank tests the engine to full kW; a reactive bank adds the alternator's full kVA.

The two load bank types load a generator differently. Which one a building needs depends on what its generator runs in an outage.

Resistive load bank

  • Tests the set to 100 percent of nameplate kW
  • Loads the cooling, fuel and exhaust systems fully
  • Reaches only 80 percent of nameplate kVA
  • Presents a unity (1.0) power factor

Reactive (inductive) load bank

  • Used with a resistive bank
  • Brings the power factor to about 0.8 on a diesel set
  • Tests the full nameplate kVA rating
  • Exercises the alternator as well as the engine

When reactive matters

  • Generators that mainly run motor-driven equipment
  • Elevator machines and fire pumps are motor loads
  • Paralleled or mission-critical systems
  • Specified by the engineer or the accreditor
  • The 80 percent figure. Load bank maker Avtron says a resistive unit can only reach 80 percent of the set's kVA rating, and an inductive unit brings the power factor below unity.Avtron, "Load Bank Basics"
  • Motor loads. Generac's white paper says generators that primarily supply motor-driven equipment and capacitors may be tested with reactive load banks.Generac white paper

Before and after

What a building manager should have ready, and what the test record should hold.

Safe photos and the existing logs are enough to start. Do not open switchgear or the generator's control panel to collect them.

Have ready

  • A nameplate photo: standby kW, kVA, voltage and phase
  • Recent monthly logs with the kW reached
  • The hour meter reading
  • Any NJDEP general permit registration
  • Where the load bank breaker or docking station is

On the day

  • Access to the generator and the transfer switches
  • Someone who can approve a transfer to emergency power
  • Staff and tenants told a test is running
  • Enough fuel for the run

The record afterwards

  • Each load step, its kW and how long it held
  • Voltage, frequency, amps, oil pressure and temperatures
  • Hour meter start and stop times
  • Problems found and the corrective action
  • The details NJDEP's log needs
  • What a test can show. Generac lists capacity to deliver the required output, voltage regulator response time, voltage and frequency stability, the control system under different loads, and oil and fuel pressure.Generac white paper
  • What a monthly record lists. A state health department's checklist includes the standby kW, 30 percent of it, ATS transfer time, cool-down delay, run time from the hour meter, oil pressure, temperatures, exhaust temperature and kW under test.Minnesota Department of Health
  • A failed test. The record names the unsatisfactory condition and the corrective action, and the repair goes to MDL's generator repair and maintenance page.

Cost

What decides the price of a load bank test, and one published range.

MDL does not publish prices, and this page lists none. These are the things that move a load bank test quote.

  • Generator size. A larger kW rating needs a larger load bank and heavier cables.
  • Test length. An annual supplemental test runs 1.5 hours at load; a 36-month test runs up to 4 hours.
  • The connection point. A ready load bank breaker or docking station is simpler than a temporary connection.
  • Resistive or reactive. A reactive test adds equipment.
  • Access. A rooftop or basement generator, or a long cable run, adds time.
  • One published figure. ThePricer, a national cost guide, lists $600 to $1,400 for a commercial load-bank test (published August 12, 2026, read November 16, 2026; it does not say which generator sizes the range covers).ThePricer

Coverage

Generator load tests for buildings in Essex, Morris and Union counties.

MDL works from 4 Harrison Avenue in West Orange. These towns in the three counties have their own MDL service-area page. Whatever the town, include the exact address so coverage can be confirmed for the building.

Generator load bank testing

Annual or 36-month test coming up, or monthly runs short of 30 percent? Call MDL.

Call or send the form with the address, the generator's nameplate details and the last monthly logs. The form opens with Generator / Backup Power chosen; pick Business / Commercial or Rental / Managed Property as the property type.

Load bank questions

Plain answers on schedules, health care rules, New Jersey test days, wet stacking and cost.

Each answer comes from the standards, regulations and manufacturer papers listed under Sources. MDL publishes no prices, and this page lists none.

What is generator load bank testing?

A load bank is a portable or permanent unit that puts an artificial electrical load on a generator and turns the energy into heat. The test steps the generator up to a set share of its nameplate kW and holds it there. Voltage, frequency, amps, kW, temperatures and oil pressure are recorded at each step. It proves the set can carry load the building does not supply on a normal day. MDL Electric Cooling & Heating does generator load bank testing for commercial standby and emergency generators in Essex, Morris and Union counties.

How often does a generator need a load bank test?

Under NFPA 110, a diesel emergency generator runs monthly for at least 30 minutes at 30 percent or more of its standby nameplate kW, or at the manufacturer's minimum exhaust temperature. A diesel set whose monthly runs fall short gets an annual supplemental load test: 50 percent for 30 minutes, then 75 percent for one hour. Level 1 systems also get a test of up to four hours at least once every 36 months. New Jersey's fire code adds an annual test of required emergency generators under anticipated load.

What are the NFPA 110 generator load bank testing requirements?

NFPA 110 (2019 edition, section 8.4.2.3, as quoted by Generac) covers diesel installations that do not meet the monthly loading rule. They are exercised annually with supplemental loads of at least 50 percent of the nameplate kW rating for 30 continuous minutes. Then the load is at least 75 percent for one continuous hour, for at least 1.5 continuous hours in all. The standard also allows a supplemental load bank to meet the 30 percent monthly requirement.

Do nursing homes and medical buildings follow different testing rules?

They add layers. CMS requires nursing homes to implement the inspection, testing and maintenance requirements of NFPA 99, NFPA 110 and the Life Safety Code (42 CFR 483.73(e)(2)). NFPA 99 asks for 12 generator tests a year, 20 to 40 days apart. The Joint Commission's EC.02.05.07 lists monthly 30-minute load tests and the annual 50 and 75 percent test when the monthly load falls short. It also lists a four-hour test at 30 percent or more every 36 months.

What does New Jersey require for emergency generator testing?

New Jersey's State Fire Prevention Code adds Section 1203.4.2.1 to the 2018 International Fire Code. Required emergency generators are tested at least annually, to the manufacturer's specifications, under anticipated load conditions. A transition test each year confirms the transfer to emergency power takes 10 seconds or less. Engine-driven emergency generators keep fuel on site for at least two hours of full-demand operation (N.J.A.C. 5:70-3.2).

Can we run a load bank test on any day?

Not always. NJDEP's general permits bar routine testing and maintenance on days it forecasts air quality anywhere in New Jersey as unhealthy for sensitive groups or worse. NJDEP says to check the forecast after 4:00 p.m. the day before and reschedule if needed. Test runs also count toward the generator's registered testing hours, which can never exceed 100 a year. In a true emergency the generator runs whatever the air quality.

What is wet stacking, and does a load test help?

Wet stacking is unburned fuel or carbon, or both, collecting in a diesel's exhaust system after light loading. NFPA's annex says continuous black smoke during a run is the sign, and that the monthly 30 percent loading is meant to reduce it. Generac's white paper says the full-load operation of a load bank test burns off excess soot and moisture. Avtron notes heavy deposits can restrict exhaust flow and reduce output or cause a shutdown.

What does 80 percent mean on a load bank test?

A resistive load bank can test a generator to 100 percent of its kW rating, but only to 80 percent of its kVA rating, according to load bank maker Avtron. An inductive load bank used with the resistive one brings the power factor to about 0.8 and tests the full kVA rating. Generac names generators that mainly supply motor-driven equipment as the ones a reactive test suits.

Will the building lose emergency power during the test?

A load bank test is set up so the building does not depend on the test cables. NFPA 110 requires equivalent test loads to be replaced automatically with the emergency loads if normal power fails. EC&M advises connecting the load bank in parallel with the building load, at a dedicated bus or connection box. It also says never to disconnect the generator's output cables during a test. MDL confirms the connection point before the test day.

What should we send to schedule a load bank test?

Send the building address, its use and who approves the work. Add a photo of the generator nameplate showing the standby kW, kVA and voltage. Add recent monthly test logs with the kW reached, the hour meter reading and any NJDEP general permit registration. Say where the load bank breaker, docking station or connection box is, if the building has one. Photos are enough; do not open switchgear to take them.

How much does a load bank test cost?

MDL does not publish prices, and this page lists none. The cost depends on the generator's size, the length of the test, where the load bank can connect, access, and whether a reactive test is needed. The cost section on this page shows one published national range with its source and the date it was read.

Which towns does MDL cover for load bank testing?

MDL works from 4 Harrison Avenue in West Orange. It covers Essex County towns including West Orange, Montclair, Bloomfield, Glen Ridge, Verona, Cedar Grove, Nutley, Belleville, Livingston, Maplewood, South Orange and Short Hills. In Morris County it covers Morristown and Chatham. In Union County it covers Union Township, Summit, Rahway, Kenilworth, Garwood and Fanwood. Send the exact address so coverage can be confirmed.

Sources

The standards, permits and papers behind the testing schedule.

All read November 16, 2026. Standards change by edition, so each line names the edition it quotes.

About this page

Who wrote this load bank page, and what it leaves to the building's own records.

MDL Electric Cooling & Heating wrote this page. MDL is a licensed electrical contractor and master HVACR contractor at 4 Harrison Ave, West Orange (NJ Electrical Business Permit #34EB01606200; NJ Electrical Contractor #34EI01606200; NJ Master HVACR Contractor #19HC00308200), working across Essex, Morris and Union counties. The page explains generator load bank testing and the rules behind it. It is not legal or engineering advice for a specific building; the fire official, construction office, NJDEP, insurer or accreditor decides what applies. No figure here is an MDL price. The worked kW examples are our arithmetic on the NFPA percentages.

Keep going

Generator and building pages that connect to this one

Generator

Commercial generator installation

A new standby system: the generator, the transfer switch, the fuel, permits and NJDEP air rules.

Learn more
Generator

Generator repair and maintenance

A generator that fails its test, will not start or will not take over, and the upkeep that keeps it ready.

Learn more
Commercial

Heat trace for pipes and sprinkler lines

Freeze protection circuits for the water and sprinkler piping in the same buildings.

Learn more
Commercial

Commercial electrician

Troubleshooting, circuits, panels and switchgear for the rest of the building.

Learn more

Request service

Send MDL the service, town, and best callback number.

Use the form for planned service or call for urgent electrical, heating, or cooling help.